Backflow assembly test: 5099 Quarry Ct
Needs reviewFiled Nov 20, 2026 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 20, 2026
- Assembly type
- DC
- Serial number
- W763534
- Size
- 3/4
- Test gauge serial
- G-8254
- Gauge calibration date
- Apr 16, 2026
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-30-01252
- Readings in range, no flags
- Result: passing. Next due date resets when approved.