Backflow assembly test: 1739 Sycamore Ct
ApprovedFiled Nov 10, 2026 by Parker Nguyen, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 10, 2026
- Assembly type
- RP
- Serial number
- W741572
- Size
- 1
- Test gauge serial
- G-7770
- Gauge calibration date
- Oct 10, 2026
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-19-01085
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1739 Sycamore Ct
Owner: Emerson Marsh
Parcel 051-19-01085