Backflow assembly test: Blue Heron Medical Offices

Approved

Filed Dec 5, 2025 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Dec 5, 2025
Assembly type
RP
Serial number
W661248
Size
1 1/2
Test gauge serial
G-8567
Gauge calibration date
Oct 6, 2025
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-54-01357
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1226 Cedar Hollow Rd
Owner: Nguyen Holdings LLC
Parcel 051-54-01357