Backflow assembly test: 8352 Old Church Trl
ApprovedFiled Jul 1, 2026 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 1, 2026
- Assembly type
- PVB
- Serial number
- W710829
- Size
- 1
- Test gauge serial
- G-2331
- Gauge calibration date
- Nov 28, 2025
- Check valve 1
- 3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-67-01239
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.