Backflow assembly test: Maple Leaf Apartments

Approved

Filed Oct 29, 2025 by Avery Ramirez, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Oct 29, 2025
Assembly type
RP
Serial number
Z473358
Size
1
Test gauge serial
G-7278
Gauge calibration date
May 29, 2025
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 051-97-01153
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.