Back to the backflow review queue
Backflow assembly test: 8510 Stone Gate Ln
ApprovedFiled Oct 25, 2024 by Avery Ramirez, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Oct 25, 2024
- Assembly type
- PVB
- Serial number
- W996650
- Size
- 3/4
- Test gauge serial
- G-6423
- Gauge calibration date
- Aug 11, 2024
- Check valve 1
- 6.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ramirez, current on the service date
- All required fields present
- Address matches parcel 051-58-01342
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8510 Stone Gate Ln
Owner: Sam Danner
Parcel 051-58-01342