Back to the backflow review queue

Backflow assembly test: 6122 Old Church Ct

Approved

Filed Jun 1, 2024 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 1, 2024
Assembly type
RP
Serial number
B302196
Size
3/4
Test gauge serial
G-7132
Gauge calibration date
Jan 17, 2024
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-66-01250
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6122 Old Church Ct
Owner: Sam Stroud
Parcel 051-66-01250