Backflow assembly test: 1756 Ridgeview Way

Approved

Filed Dec 25, 2024 by Avery Ramirez, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Dec 25, 2024
Assembly type
DC
Serial number
Z877093
Size
3/4
Test gauge serial
G-6171
Gauge calibration date
Nov 8, 2024
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 051-91-01256
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.