Back to the backflow review queue

Backflow assembly test: 5240 Quarry Dr

Approved

Filed Apr 9, 2025 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 9, 2025
Assembly type
RP
Serial number
Z707553
Size
1
Test gauge serial
G-9364
Gauge calibration date
Oct 17, 2024
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-76-01321
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5240 Quarry Dr
Owner: Reese Ellery
Parcel 051-76-01321