Back to the backflow review queue
Backflow assembly test: 2569 Orchard Dr
ApprovedFiled Aug 10, 2026 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 10, 2026
- Assembly type
- PVB
- Serial number
- W972565
- Size
- 3/4
- Test gauge serial
- G-4053
- Gauge calibration date
- Jan 14, 2026
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-41-01210
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2569 Orchard Dr
Owner: Hayden Danner
Parcel 051-41-01210