Backflow assembly test: 6356 Orchard Ln
ApprovedFiled May 1, 2025 by Parker Harlow, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- May 1, 2025
- Assembly type
- DC
- Serial number
- A584046
- Size
- 1
- Test gauge serial
- G-6860
- Gauge calibration date
- Dec 1, 2024
- Check valve 1
- 3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Harlow, current on the service date
- All required fields present
- Address matches parcel 041-55-01232
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6356 Orchard Ln
Owner: Jamie Wexler
Parcel 041-55-01232