Backflow assembly test: Crossroads Car Wash

Approved

Filed Nov 24, 2024 by Casey Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Nov 24, 2024
Assembly type
DC
Serial number
W186518
Size
1
Test gauge serial
G-1075
Gauge calibration date
Oct 13, 2024
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Fairley, current on the service date
  • All required fields present
  • Address matches parcel 041-55-01298
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.