Back to the backflow review queue

Backflow assembly test: 4688 Pine Knoll Rd

Approved

Filed Nov 10, 2026 by Casey Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Nov 10, 2026
Assembly type
RP
Serial number
A535134
Size
3/4
Test gauge serial
G-6833
Gauge calibration date
May 26, 2026
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Fairley, current on the service date
  • All required fields present
  • Address matches parcel 041-47-01222
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4688 Pine Knoll Rd
Owner: Logan Wexler
Parcel 041-47-01222