Backflow assembly test: Blue Heron Animal Hospital

Approved

Filed Jan 11, 2026 by Parker Ashby, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jan 11, 2026
Assembly type
RP
Serial number
A933025
Size
1 1/2
Test gauge serial
G-1478
Gauge calibration date
Jun 4, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 041-56-01085
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.