Back to the backflow review queue
Backflow assembly test: 1960 Meadow Lark Trl
Needs reviewFiled Nov 21, 2026 by Parker Harlow, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 21, 2026
- Assembly type
- RP
- Serial number
- A646434
- Size
- 1
- Test gauge serial
- G-5876
- Gauge calibration date
- Nov 17, 2025
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 1.5 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Harlow, current on the service date
- All required fields present
- Address matches parcel 041-34-01046
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Property
1960 Meadow Lark Trl
Owner: Jamie Lindqvist
Parcel 041-34-01046