Backflow assembly test: 1742 Orchard Ct

Approved

Filed Jul 30, 2025 by Casey Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Jul 30, 2025
Assembly type
RP
Serial number
W970934
Size
3/4
Test gauge serial
G-6085
Gauge calibration date
Feb 23, 2025
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Fairley, current on the service date
  • All required fields present
  • Address matches parcel 041-85-01089
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.