Backflow assembly test: 2866 Orchard Dr

Approved

Filed Apr 29, 2025 by Quinn Nguyen, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Apr 29, 2025
Assembly type
RP
Serial number
Z875001
Size
1
Test gauge serial
G-8855
Gauge calibration date
Oct 11, 2024
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 041-71-01036
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2866 Orchard Dr
Owner: Blake Danner
Parcel 041-71-01036