Back to the backflow review queue
Backflow assembly test: 5181 Stone Gate Rd
ApprovedFiled Dec 27, 2024 by Parker Ashby, Valley Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Dec 27, 2024
- Assembly type
- RP
- Serial number
- W317125
- Size
- 3/4
- Test gauge serial
- G-6071
- Gauge calibration date
- Sep 8, 2024
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Ashby, current on the service date
- All required fields present
- Address matches parcel 041-62-01150
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
5181 Stone Gate Rd
Owner: Casey Pruitt
Parcel 041-62-01150