Backflow assembly test: 9864 Sycamore Trl

Approved

Filed Mar 4, 2026 by Quinn Nguyen, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Mar 4, 2026
Assembly type
RP
Serial number
W636252
Size
3/4
Test gauge serial
G-2649
Gauge calibration date
Jan 5, 2026
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 041-22-01336
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9864 Sycamore Trl
Owner: Blake Ellery
Parcel 041-22-01336