Back to the backflow review queue

Backflow assembly test: 9222 Fox Run Rd

Approved

Filed Jun 16, 2026 by Quinn Nguyen, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Jun 16, 2026
Assembly type
RP
Serial number
A428194
Size
1
Test gauge serial
G-6240
Gauge calibration date
Sep 16, 2025
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 041-84-01286
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9222 Fox Run Rd
Owner: Riley Ellery
Parcel 041-84-01286