Backflow assembly test: 4607 Spring Branch Ln
Needs reviewFiled Nov 21, 2026 by Casey Fairley, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 21, 2026
- Assembly type
- RP
- Serial number
- K641153
- Size
- 3/4
- Test gauge serial
- G-8995
- Gauge calibration date
- Aug 15, 2026
- Check valve 1
- 8.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Fairley, current on the service date
- All required fields present
- Address matches parcel 041-89-01143
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
4607 Spring Branch Ln
Owner: Riley Ashby
Parcel 041-89-01143