Back to the backflow review queue

Backflow assembly test: 9839 Orchard Dr

Approved

Filed Sep 18, 2025 by Avery Wexler, Northstar Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 18, 2025
Assembly type
RP
Serial number
W561789
Size
3/4
Test gauge serial
G-9436
Gauge calibration date
Jun 8, 2025
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Wexler, current on the service date
  • All required fields present
  • Address matches parcel 041-11-01240
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9839 Orchard Dr
Owner: Drew Okafor
Parcel 041-11-01240