Backflow assembly test: 3429 Orchard Ln

Approved

Filed Sep 29, 2024 by Parker Whitcomb, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 29, 2024
Assembly type
RP
Serial number
A465020
Size
1
Test gauge serial
G-4368
Gauge calibration date
Dec 16, 2023
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 037-46-01266
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3429 Orchard Ln
Owner: Jordan Ashby
Parcel 037-46-01266