Backflow assembly test: 386 Orchard Trl
ApprovedFiled Jun 1, 2025 by Parker Whitcomb, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 1, 2025
- Assembly type
- PVB
- Serial number
- A505328
- Size
- 1
- Test gauge serial
- G-9163
- Gauge calibration date
- Sep 20, 2024
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Whitcomb, current on the service date
- All required fields present
- Address matches parcel 037-57-01118
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
386 Orchard Trl
Owner: Casey Hollins
Parcel 037-57-01118