Back to the backflow review queue
Backflow assembly test: Two Rivers Dental
ApprovedFiled Dec 31, 2025 by Parker Whitcomb, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Dec 31, 2025
- Assembly type
- DC
- Serial number
- Z145177
- Size
- 4
- Test gauge serial
- G-9979
- Gauge calibration date
- Sep 21, 2025
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Whitcomb, current on the service date
- All required fields present
- Address matches parcel 037-99-01256
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
9870 Orchard Dr
Owner: Ashby Holdings LLC
Parcel 037-99-01256