Back to the backflow review queue

Backflow assembly test: 6547 Hickory Ct

Approved

Filed Oct 11, 2026 by Drew Kessler, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Oct 11, 2026
Assembly type
PVB
Serial number
K968783
Size
3/4
Test gauge serial
G-9788
Gauge calibration date
Mar 16, 2026
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Kessler, current on the service date
  • All required fields present
  • Address matches parcel 037-41-01078
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6547 Hickory Ct
Owner: Logan Ashby
Parcel 037-41-01078