Backflow assembly test: 2685 Spring Branch Way

Approved

Filed Jan 10, 2026 by Parker Vance, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jan 10, 2026
Assembly type
DC
Serial number
W774286
Size
3/4
Test gauge serial
G-4042
Gauge calibration date
Aug 11, 2025
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-95-01230
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2685 Spring Branch Way
Owner: Riley Whitcomb
Parcel 037-95-01230