Back to the backflow review queue

Backflow assembly test: 6904 Old Church Ct

Approved

Filed Sep 25, 2025 by Hayden Pruitt, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 25, 2025
Assembly type
PVB
Serial number
B872452
Size
3/4
Test gauge serial
G-3114
Gauge calibration date
Jan 4, 2025
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 037-22-01050
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6904 Old Church Ct
Owner: Hayden Lindqvist
Parcel 037-22-01050