Backflow assembly test: 1435 Sycamore Trl

Approved

Filed Oct 14, 2024 by Emerson Hollins, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Oct 14, 2024
Assembly type
RP
Serial number
A719670
Size
3/4
Test gauge serial
G-6027
Gauge calibration date
Feb 4, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Hollins, current on the service date
  • All required fields present
  • Address matches parcel 025-94-01207
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.