Backflow assembly test: 1553 Quarry Dr
ApprovedFiled Oct 2, 2024 by Hayden Marsh, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 2, 2024
- Assembly type
- RP
- Serial number
- Z263639
- Size
- 1
- Test gauge serial
- G-9752
- Gauge calibration date
- Jul 31, 2023
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Marsh, current on the service date
- All required fields present
- Address matches parcel 025-25-01022
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.