Backflow assembly test: 3904 Meadow Lark Ct

Approved

Filed May 27, 2026 by Emerson Ellery, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 27, 2026
Assembly type
RP
Serial number
W208451
Size
3/4
Test gauge serial
G-4694
Gauge calibration date
Dec 31, 2025
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Ellery, current on the service date
  • All required fields present
  • Address matches parcel 025-85-01216
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3904 Meadow Lark Ct
Owner: Logan Pruitt
Parcel 025-85-01216