Back to the backflow review queue

Backflow assembly test: 2694 Cedar Hollow Ct

Approved

Filed Sep 2, 2025 by Blake Pruitt, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Sep 2, 2025
Assembly type
RP
Serial number
W572489
Size
1
Test gauge serial
G-3149
Gauge calibration date
May 2, 2025
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 025-42-01007
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2694 Cedar Hollow Ct
Owner: Logan Okafor
Parcel 025-42-01007