Approved

Filed Sep 25, 2024 by Blake Pruitt, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 25, 2024
Assembly type
RP
Serial number
W500932
Size
1
Test gauge serial
G-5849
Gauge calibration date
May 23, 2023
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 025-37-01103
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.