Backflow assembly test: 9190 Turkey Hill Ct

Approved

Filed Nov 23, 2025 by Drew Stroud, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Nov 23, 2025
Assembly type
RP
Serial number
W819309
Size
3/4
Test gauge serial
G-9598
Gauge calibration date
Mar 10, 2025
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Stroud, current on the service date
  • All required fields present
  • Address matches parcel 025-92-01157
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9190 Turkey Hill Ct
Owner: Shawn Marsh
Parcel 025-92-01157