Backflow assembly test: Station Market
ApprovedFiled Jul 8, 2026 by Reese Fairley, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 8, 2026
- Assembly type
- RP
- Serial number
- A182788
- Size
- 2
- Test gauge serial
- G-4934
- Gauge calibration date
- Dec 26, 2025
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Fairley, current on the service date
- All required fields present
- Address matches parcel 025-24-01195
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5553 Quarry Trl
Owner: Lindqvist Holdings LLC
Parcel 025-24-01195