Back to the backflow review queue
Backflow assembly test: 4525 Ridgeview Trl
ApprovedFiled Sep 24, 2026 by Hayden Marsh, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 24, 2026
- Assembly type
- RP
- Serial number
- Z840246
- Size
- 1
- Test gauge serial
- G-9821
- Gauge calibration date
- Apr 19, 2026
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Marsh, current on the service date
- All required fields present
- Address matches parcel 025-65-01343
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
4525 Ridgeview Trl
Owner: Jordan Vance
Parcel 025-65-01343