Back to the backflow review queue

Backflow assembly test: Crossroads Brewing Co

Approved

Filed Apr 6, 2026 by Drew Stroud, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Apr 6, 2026
Assembly type
RP
Serial number
B446324
Size
4
Test gauge serial
G-2510
Gauge calibration date
Aug 9, 2025
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
3.5 psid
Relief valve opened at
2.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Stroud, current on the service date
  • All required fields present
  • Address matches parcel 025-89-01282
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7030 Mill Creek Ct
Owner: Harlow Holdings LLC
Parcel 025-89-01282