Backflow assembly test: Crossroads Brewing Co

Approved

Filed Apr 18, 2025 by Reese Fairley, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Apr 18, 2025
Assembly type
RP
Serial number
B446324
Size
4
Test gauge serial
G-7485
Gauge calibration date
Jan 8, 2025
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 025-89-01282
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.