Back to the backflow review queue

Backflow assembly test: 4620 Laurel Way

Approved

Filed Nov 9, 2026 by Parker Benton, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Nov 9, 2026
Assembly type
RP
Serial number
A507586
Size
3/4
Test gauge serial
G-9232
Gauge calibration date
Apr 2, 2026
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Benton, current on the service date
  • All required fields present
  • Address matches parcel 025-15-01234
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4620 Laurel Way
Owner: Quinn Harlow
Parcel 025-15-01234