Backflow assembly test: 5329 Pine Knoll Way

Approved

Filed Sep 29, 2025 by Drew Stroud, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 29, 2025
Assembly type
PVB
Serial number
A395191
Size
1
Test gauge serial
G-9638
Gauge calibration date
Jul 8, 2024
Check valve 1
0 psid
Check valve 1 closed tight
No
Check valve 2
2.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Stroud, current on the service date
  • All required fields present
  • Address matches parcel 025-19-01350
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5329 Pine Knoll Way
Owner: Taylor Fairley
Parcel 025-19-01350