Backflow assembly test: 8706 Cedar Hollow Way
ApprovedFiled Sep 5, 2026 by Avery Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 5, 2026
- Assembly type
- RP
- Serial number
- W582744
- Size
- 3/4
- Test gauge serial
- G-2894
- Gauge calibration date
- May 11, 2026
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Vance, current on the service date
- All required fields present
- Address matches parcel 025-77-01071
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
8706 Cedar Hollow Way
Owner: Jordan Calloway
Parcel 025-77-01071