Back to the backflow review queue
Backflow assembly test: 9711 Sycamore Dr
ApprovedFiled Apr 6, 2026 by Hayden Marsh, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Apr 6, 2026
- Assembly type
- RP
- Serial number
- A145592
- Size
- 1
- Test gauge serial
- G-4617
- Gauge calibration date
- Sep 6, 2025
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Marsh, current on the service date
- All required fields present
- Address matches parcel 025-93-01016
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9711 Sycamore Dr
Owner: Parker Whitcomb
Parcel 025-93-01016