Back to the backflow review queue
Backflow assembly test: 1926 Fox Run Trl
ApprovedFiled May 12, 2023 by Emerson Ellery, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 12, 2023
- Assembly type
- RP
- Serial number
- W526821
- Size
- 3/4
- Test gauge serial
- G-7855
- Gauge calibration date
- Feb 6, 2023
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Ellery, current on the service date
- All required fields present
- Address matches parcel 025-45-01224
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
1926 Fox Run Trl
Owner: Jamie Lindqvist
Parcel 025-45-01224