Back to the backflow review queue
Backflow assembly test: 1059 Laurel Rd
ApprovedFiled Sep 8, 2026 by Drew Stroud, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 8, 2026
- Assembly type
- DC
- Serial number
- Z713917
- Size
- 3/4
- Test gauge serial
- G-1574
- Gauge calibration date
- May 27, 2026
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Stroud, current on the service date
- All required fields present
- Address matches parcel 025-39-01163
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1059 Laurel Rd
Owner: Riley Harlow
Parcel 025-39-01163