Backflow assembly test: 7725 Turkey Hill Dr
ApprovedFiled Sep 5, 2024 by Reese Fairley, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 5, 2024
- Assembly type
- RP
- Serial number
- B589222
- Size
- 3/4
- Test gauge serial
- G-5182
- Gauge calibration date
- Apr 9, 2024
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Fairley, current on the service date
- All required fields present
- Address matches parcel 025-66-01054
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.