Backflow assembly test: 2668 Old Church Ln
ApprovedFiled May 12, 2026 by Avery Ashby, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- May 12, 2026
- Assembly type
- RP
- Serial number
- A503713
- Size
- 1
- Test gauge serial
- G-3046
- Gauge calibration date
- Jan 22, 2026
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ashby, current on the service date
- All required fields present
- Address matches parcel 017-46-01149
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.