Back to the backflow review queue

Backflow assembly test: 3594 Stone Gate Ct

Approved

Filed Jun 24, 2026 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jun 24, 2026
Assembly type
RP
Serial number
Z276915
Size
1
Test gauge serial
G-4452
Gauge calibration date
Oct 17, 2025
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-47-01270
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3594 Stone Gate Ct
Owner: Logan Marsh
Parcel 017-47-01270