Back to the backflow review queue

Backflow assembly test: 3594 Stone Gate Ct

Approved

Filed Jun 18, 2025 by Riley Brandt, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 18, 2025
Assembly type
RP
Serial number
Z276915
Size
1
Test gauge serial
G-8090
Gauge calibration date
Sep 1, 2024
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Brandt, current on the service date
  • All required fields present
  • Address matches parcel 017-47-01270
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3594 Stone Gate Ct
Owner: Logan Marsh
Parcel 017-47-01270