Backflow assembly test: 4347 Pine Knoll Trl

Approved

Filed Nov 27, 2024 by Avery Wexler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Nov 27, 2024
Assembly type
PVB
Serial number
B679080
Size
1
Test gauge serial
G-2660
Gauge calibration date
Feb 4, 2024
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Wexler, current on the service date
  • All required fields present
  • Address matches parcel 017-36-01191
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4347 Pine Knoll Trl
Owner: Jamie Okafor
Parcel 017-36-01191