Backflow assembly test: 1378 Old Church Ln

Approved

Filed Apr 16, 2026 by Riley Brandt, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 16, 2026
Assembly type
DC
Serial number
W751491
Size
3/4
Test gauge serial
G-2549
Gauge calibration date
Oct 29, 2025
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Brandt, current on the service date
  • All required fields present
  • Address matches parcel 017-32-01312
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1378 Old Church Ln
Owner: Morgan Marsh
Parcel 017-32-01312